Jenereithara ea Hona Joale ea GDCL-10kA Impulse
●Mocheso oa tikoloho: -10 ℃ ho isa ho 40 ℃
●Mongobo o amanang: ≤ 85% RH
●Boima: ≤ 1000m
●Tšebeliso ea ka tlung
●Ha ho lerōle la conductive, ha ho mollo kapa kotsi e phatlohang, ha ho tšepe e senyang kapa khase e kenang.
●Power voltage waveform ke sine wave, sekhahla sa ho sotha <5%
●Khahlano ea lefats'e ha e fete 1Ω.
IEC60099-4: 2014 Surge Arresters-Karolo ea 4: Metal-oxide surge e tšoaroang ntle le likheo bakeng sa litsamaiso tsa ac.
GB311.1-1997 Khokahano ea Insulation ea phetisetso ea Matla a HV le phetoho.
IEC 60060-1 Teko ea Teko ea Voltage e Phahameng - Tlhokahalo ea Teko e Akaretsang.
Mokhoa oa ho lekanya oa IEC 60060-2 - Sistimi ea Tekanyo ea Motlakase o Phahameng.
GB/T16896.1-1997 Digital Recorder ea High Voltage Impulse Test.
DLT992-2006 Ho phethahatsa Melao bakeng sa Tekanyo ea Voltage ea Impulse.
DL/T613-1997 Litlhaloso tsa tekheniki bakeng sa ho ts'oaroa ha AC gapless metal oxide e tsoang kantle ho naha.
Ka ho sebelisa lipotoloho tsa LC le RL, capacitor C e qosoang e tsoa ho mojaro o sa tsitsang oa ho hanyetsa ka inductance L le ho hanyetsa R ho hlahisa tšusumetso ea hona joale e lumellanang le litlhoko tse tloaelehileng.
●Mokhoa oa hona joale oa maqhubu: 8/20μs
●E lekantsoe hona joale: 10kA
●Mokhoa oa ho khantša: sebaka sa bolo ea phefumoloho.Taolo ea othomathiki, taolo ea matsoho.
●Polarity ea hajoale: e ntle.Pontšo ea waveform: ha joale-e mpe;residual voltage-positive.
●Tekanyo ea hajoale: Khoeli ea Rogowski (0-50kA), ho nepahala: 1%.
●Tekanyo ea matla a setseng: karohano ea matla a ho hanyetsa (0-100kV), ho nepahala: 1%
●Ho nepahala ha tekanyo ka kakaretso: 3%
●Pontšo ea waveform: Oscilloscope (Tektronix) le PC.
●Oscilloscope le capacitor charging voltage li behiloe ho PC ka senotlolo se le seng.
●Polokelo ea data: ho PC.Lintlha tsa tekanyo le waveform li bokelloa ka oscilloscope, ebe li fetisetsoa ho PC ka boema-kepe ba USB, 'me li bolokoa joalo ka sebopeho sa Excel foldareng e seng e setiloe ho hard disk ea komporo.
●Tšireletso ea ts'ireletso: over-voltage, over-current, khokahano ea taolo ea phihlello, setopong sa tšohanyetso, motheo oa othomathike.E na le mochini oa ho theola matsoho: basebetsi ba ts'ebetso ba tlameha ho tsoa ka bar ea ho theola pele ba ikopanya le 'mele oa jenereithara, ba nkela mochini o hanyetsanang le waveform, ho nkela ntho ea teko sebaka, ho lokisa, joalo-joalo, le ho hokahanya bar e thellang ho pheletso ea 'mele ea HV.
●Ho hanyetsa fatše: ≤1Ω
●Phepelo ea matla: 220V ± 10%, 50Hz;matla a 10kVA
Yuniti ea ho tjhaja
1) Mokhoa oa ho tjhaja: ho lokisoa ha maqhubu a halofo ka nako e sa fetoheng ho potoloho ea LC ka lehlakoreng la mantlha la transformer.Lehlakore la mantlha le na le tšireletso ea potoloho e khuts'oane/moroalo o fetang.
2) High-voltage rectifier diode: reverse voltage 150kV, Max.Karolelano ea hajoale 0.2A.
3) Transformer motlakase o ka sehloohong oa 220V, motlakase oa bobeli 50kV, matla a lekantsoeng 10kVA.
4) Mohanyetsi o sirelletsang oa ho tjhaja: terata ea ho hanyetsa enameled e na le leqeba le letenya ka har'a tube ea insulation.
5) Sesebelisoa sa kamehla sa ho tjhaja: ka har'a 10 ~ 100% e lekantsoe matla a ho tjhaja, ho nepahala ho feto-fetohang ha motlakase oa ho tjhaja ke 1%, 'me ho nepahala ha sebele ho tjhaja ho molemo ho feta 1%.
6) Tlhokomelo ea motlakase oa capacitor: DC resistance voltage divider e sebelisa khalase ea uranium e hanyetsang le khanyetso ea filimi ea tšepe.Letšoao la motlakase la letsoho le tlaase-voltage le fetisetsoa tsamaisong ea ho lekanya ka cable e sirelelitsoeng.
Yuniti ea ho lahla
1) Sesebelisoa sa ho theola 'mele: ha tlhahlobo e emisoa kapa lebaka lefe kapa lefe le etsa hore taolo ea phihlello e bulehe, terminal ea motlakase e phahameng e ka theoa ka bo eona ke mochini o sireletsang mme ea lokolloa kapele.
2) Sesebelisoa sa ho lahla se amohela karohano ea valve ea pneumatic solenoid le mokhoa oa ho theola fatše, o nang le sebopeho sa compact, botsitso bo matla ba phetisetso le ketso e tšepahalang.
3) Sebaka sa ho ntša metsi se entsoe ka graphite e nang le ho hanyetsa mocheso o matla le ho hanyetsa hona joale ho hoholo.
Jenereithara
1) Li-capacitor tse 'ne tsa polokelo ea matla li arotsoe ka lihlopha tse peli' me li behiloe holim'a bracket ea chassis ea insulated ka ho latellana.Inductance ea wave-front le ho hanyetsa maqhubu a maqhubu ka ho latellana ho tsitsitse libakeng tse lumellanang, tse bonolo, tse hlakileng, tse tiileng le tse ka tšeptjoang.
2) Sesebelisoa sa clamping sa ntho ea tlhahlobo se matlafatsoa ke pusher ea moea.
3) Sesebelisoa sa ho khantša se nka likarolo tsa moea ho tsamaisa sebaka se ka thōko sa bolo le ho tsoa ka lekhalo la bolo, le tsitsitseng le le ka tšeptjoang.
1) Matla a setseng: karohano ea matla a ho hanyetsa, khanyetso e sa tsitsang, ho nepahala ho phahameng, Max.voltage ke 30kV, e na le thapo e lekanyang ea 1pc 75Ω, 5meters.
2) Hajoale: Ho sebelisa khoele ea Rogowski e nang le thapo ea ho lekanya ea 100kA le 1pc 75Ω, 5meters.
3) Oscilloscope: Ho sebelisa Tektronix DPO2002B, tekanyo ea sampole ea 1GS / s, 100MHz broadband, mechine e 'meli.
4) Software: e na le tsamaiso ea hona joale ea tekanyo ea ICG impulse, e nang le data le waveform ho bala / ho boloka le ho bala mesebetsi.
Setsi sa Taolo
1) Mofuta oa tafole ea Workbench e thusa basebetsi ba ts'ebetso ho sebetsa ba lutse, ba le bonolo haholoanyane.
2) Khabinete e na le li-casters tse tsamaeang le tšehetso e tsitsitseng, e ka thusang ho sisinyeha le ho lokisa maemo.
3) Moralo o nepahetseng oa sistimi ea taolo, sebopeho se bonolo sa basebelisi, li-buttons tsa 3 feela (tefiso, ho lahla, ho chesa) le switch switch (phetoho ea waveform e mene), ts'epo e phahameng, sebopeho se bonolo, se bonolo ho sebetsa, ho le bonolo ho se boloka.
4) Setlhophiso sa Oscilloscope se laoloa ke k'homphieutha 'me se phethoa ka senotlolo se le seng, se qobang ts'ebetso e rarahaneng ea letsoho (oscilloscope e na le mesebetsi e mengata, eo ho leng thata ho batho bao e seng litsebi ho e laola).
5) Capacitor charging voltage e laoloa ke komporo, e nang le sebopeho se hlakileng le ts'ebetso e bonolo.
6) Oscilloscope e theha khokahano ea puisano le komporo, data ea tekanyo le waveform li bolokoa ka bo eona komporong, 'me tokomane ea Excel e hlahisoa ka bo eona.
7) Phepelo ea matla ea tsamaiso ea taolo: e arotsoe ke transformer le filter.
8) Tšireletso: ho feta-voltage, over-current, ho hokahanya ha taolo ea phihlello, ho emisa ts'ohanyetso, ho theola othomathike, joalo-joalo.
Software ea tlhahlobo e etselitsoe tlhahlobo ea hajoale e ka ipalla waveform le data ka ho buisana le oscilloscope le ho lekola waveform ho latela mokhoa oa ho lekanya oa IEC1083-2 standard.Tlhōrō ea hajoale, tlhoro ea motlakase, nako ea maqhubu a pele le nako ea ho qetela ea maqhubu li baloa ka bohona 'me li hlahisoa skrineng sa komporo hammoho le sebopeho sa maqhubu a liteko.
Lintlha le waveform li ka bolokoa ka bohona le khafetsa (ho thunya ka tšohanyetso sebakeng sa liteko)