GDSF-411CPD SF6 Gas Comprehensive Analyzer
Tlhaloso: GDSF-411CPD SF6Gas comprehensive analyzer ke sesebelisoa se nkehang habonolo se etselitsoeng ho lekanya SF6phoka ea khase, bohloeki le sehlahisoa sa ho bola.Karolo ea mantlha e nang le mokhoa oa seipone se pholileng e sebelisoa ho leka ntlha ea phoka, sensor ea Europe e nang le mokhoa oa infrared ho leka SF.6bohloeki ba khase le sensor ea electrochemical ho tloha Membrapor ho hlahloba SF6sehlahisoa sa ho bola ha khase.Ntle le moo, re boetse re amohela li-chips tsa profeshenale le li-algorithms tsa software tse ntle haholo tsa STMicroelectronics.
SF6Mongobo
Mokhoa oa ho lekanya | Mokhoa oa seipone se hatselitsoeng (Stirling Refrigeration) |
Lekhalo la litekanyo | Phoka -100℃--+20℃(90s bakeng sa tekanyo ea ntlha e le 'ngoe), phoso: e betere ho feta ±0.2℃ |
Pheta-bokgoni | ± 0.1 ℃ |
Qeto | 0.01℃ |
Pontšo yuniti | ℃, ppm, ℃ P20(boleng bo fetotsoeng ho 20 ℃) |
SF6Bohloeki
Mokhoa oa ho lekanya | Molao-motheo oa Tekanyo ea Infrared (NDIR series sensors) |
Lekhalo la ho lekanya | 0 ~ 100% SF6, phoso: e betere ho feta ± 0.3%FS |
Nako ea ho arabela | [90%] 60s |
Pheta-pheta | ± 0.3% |
Qeto | 0.01% |
Pontšo yuniti | % |
SF6Lihlahisoa tsa ho bola
Mokhoa oa ho lekanya | Molao-motheo oa Tekanyo ea Motlakase (Li-sensor tsa Electrochemical series tse tsoang ho Membrapor) |
Lekhalo la litekanyo | SO2: 0 ~ 200ppmv H2S: 0 ~ 200ppmv CO: 0 ~ 500ppmv HF: 0 ~ 50ppmv |
Ho nepahala | SO2: 10ppmv ± 3% H2S: 10ppmv ±3% CO: 50ppmv ±4% HF: 10ppmv ±3% |
Pheta-bokgoni | SO2: 10ppmv ± 2% H2S: 10ppmv ±2% CO: 50ppmv ±2% HF: 10ppmv ±2% |
Qeto | 0.01ppmv |
Pontšo yuniti | ppmv |
Kakaretso Parameters
Phepelo ea motlakase | 220VAC ± 10%, 50Hz, AC/DC ts'ebeliso, ts'ebetso e tsoelang pele e feta lihora tse 8. |
Sebelisa mocheso oa tikoloho | -20-+60 ℃ |
Mongobo wa tikoloho | 90% RH |
Tšusumetso ea boleng ba tekanyo | Ha ho phello ea khatello le phallo |
Boemo | 570*420*280mm |
Boima ba 'mele | Ha e fete 20kg. |
Mohlahlobi ea ka Sehloohong | 1 sengoathoana |
Adapter | 1 sete |
Pipe ea Teflon (e kenyelletsa valve ea phetoho ea phallo le sehokelo se potlakileng) | 1 sete |
Pipe ea mohatla | 1 sete |
Likarolo tsa tlatsetso | 1 sete |
Charger | 1 sengoathoana |
Tataiso ea mosebelisi | 1 sengoathoana |
Tlaleho ea Tlhahlobo | 1 sengoathoana |