GDKC-15 Series Circuit Breaker Analyzer
High voltage circuit breaker ke e 'ngoe ea lisebelisoa tsa bohlokoa tsa taolo tsamaisong ea matla.GDKC-15 Series e sebelisoa ho lekola litšobotsi tse matla tsa sekhahla se phahameng sa motlakase.Ho bonolo ho sebetsa, ka ho nepahala ho phahameng.
GDKC-15A | GDKC-15B | GDKC-15C | GDKC-15D | GDKC-15E | GDKC-15F | GDKC-15G | GDKC-15H | |
Ho kopana le tšepe | 12 | 12 | 12 | 12 | 12 | 12 | 12 | 12 |
Khanyetso e koalang | 6 | 6 | 6 | 6 | 6 | 6 | 6 | |
Khokahano ea graphite | 3 | 3 | 3 | 3 | 6 | |||
Motheo o phethiloeng habeli | 3 | 3 | 3 | 6 | ||||
Matla a ho hanyetsa (Sehanyetsi sa pele ho ho kenya) | 1 | 1 | 3 | 3 | 3 | 3 | 6 | |
Khanyetso e tsitsitseng | 1 | 1 | 3 | 3 | 3 | 3 | 6 | |
Khanyetso e fatshe | 3 | 6 |
●E loketse tlhahlobo ea mochini ea mefuta eohle ea li-switches tsa SF6, lisebelisoa tsa motsoako oa GIS, li-vacuum switch le li-switches tsa oli.
●Bokhoni bo matla ba ho thibela tšitiso.E ka lekoa habonolo le ho lekanngoa ka nepo seteisheneng sa 500KV.
●Accelerometer (ka boikhethelo), sensor ea mohala, sensor ea rotary, ho bonolo ho e kenya ebile e bonolo.
●Lintlha tsohle tsa tlhahlobo ea sebopeho sa mochini oa switch le 'mapa o lumellanang oa waveform li fumanoa kamora hore switch e kenngoe hang.
●Boloka lintlha tsa tlhahlobo ea tšimo le oache ea nako ea 'nete e hahelletsoeng kahare, e loketseng ho bolokoa le ho boloka letsatsi le nako ea tlhahlobo.
●Ka skrine ea LCD ea 10.1inch, e bonts'a lintlha tsohle le 'mapa, e nang le leseli le ka morao, phetoho ea phapang ea LCD le ho tima mohopolo.
●Ts'ebetso ea menyu e bonolo, e bonolo ho e sebelisa.Ka printa e hahelletsoeng ho hatisa kapele liphetho tsohle tsa data.
●E na le software ea taolo ea tlhahlobo ea data, e ka sebetsoang inthaneteng ka PC, e nang le faele ea sebopeho sa WORD.Liphetho tsa liteko li ka hlahisoa ho mefuta eohle ea lihatisi tse hatisang litlaleho tsa liteko ho etsa hore tlhahlobo ea tšimo e be komporong.
●Khetho ea ho bula le ho koala lebelo le ts'ebetso e hlalositsoeng ke mosebedisi e behiloeng ho latela litlhoko, e loketseng tekanyo ea lebelo la mofuta ofe kapa ofe oa li-switches.
●Nako:
Mabitso a 12 ka tlholeho a butse (ho koaleha).
Mokhahlelong oa ho amahanya
Khokahano ea mohato le mohato
●E koala hape:
CO, OC, nako ea COC,
Nako ea pele ea ho bula, nako ea pele ea ho koala, nako ea bobeli ea ho koala, nako ea ho bula, nako e shoeleng, ha ho nako ea hona joale.
●Bouncing:
Koala nako, linako, ts'ebetso le sebopeho sa maqhubu a mabitso ka 'ngoe.
Ho bula amplitude ea rebound ea lebitso le leng le le leng.
Velocity: lebelo ha o kopana le ho bula feela le ho koala feela, lebelo le phahameng, mokhoa oa ho tsamaea ka nako.
Maeto: leeto le felletseng, sebaka se bulehileng, maeto a ho feta, leeto le fetang le le leng, amplitude e khutlang.
Hona joale: bula / koala hona joale, setšoantšo sa hona joale sa waveform sa coil e bulehileng / e koalehileng.
Matla a sebetsang: DC0 ~ 300V / 20A e hahiloeng ka har'a dijithale, mohloli oa matla o feto-fetohang oa sekhechana, ka boiketsetso e phethela tlhahlobo ea ketso ea LV ea sekhechana sa potoloho le ho lekanya boleng ba motlakase oa sekhechana sa potoloho.
Khanyetso e koalang: nako ea pele ho nako, sebopeho sa wave wave le boleng ba ho hanyetsa ba mohanyetsi ea koalang oa batho ba 6.(ka boikhethelo)
Ho ikopanya le graphite: nako e bulehileng, ea ho koala le waveform e matla ea mochine oa puisano oa graphite oa Siemens o nang le mabitso a 3 kapa a 6. (khetho)
Motheo o phethiloeng habeli: ka tlas'a 3 kapa 6-way dual-port grounding, e ka lekanya ka nepo nako ea ho bula le ea ho koala.(ka boikhethelo)
Khanyetso e tsitsitseng: 1 * 100A tekanyo ea khanyetso ea ho kopana.
Ho hanyetsa matla (Pre-insertion resistor): 1 * 100A phetoho ea waveform ea ho hanyetsa ka matla nakong ea ketso ea potoloho ea potoloho.
●Tikoloho ea Tšebeliso
Matla a Kenang: 220V±10%, 50Hz±10%, Khatello ea Moea: 86-106kpa
Mocheso: -10-40℃ Mongobo: ≤80%RH
●Tshireletso Tshebetso
Khanyetso ea Insulation>2MΩ
Matla a Dielectric: Shell e khona ho mamella voltage frequency voltage 1.5kV ka motsotso o le mong ntle le flashover le arcing.
●The Basic Parameters
Nako: Range 20000.0ms, resolution 0.01ms, phoso 0.5%
Ho koala khanyetso: sebaka sa 10kΩ, min.qeto 1Ω, phoso 0.5% (ho ikhethela)
Ho ikopanya le graphite: sebaka sa 200ms, min.qeto 0.1ms, phoso 0.5% (ho ikhethela)
Mehato e habeli: sebaka sa 200ms, min.qeto 0.1ms, phoso 0.5% (ho ikhethela)
Khanyetso e tsitsitseng: sebaka sa 1uΩ~10mΩ, min.qeto 0.01μΩ, phoso 0.5%
Khanyetso e matla: sebaka sa 10mΩ, min.qeto 1μΩ, phoso 0.5%
Teko ea hajoale: DC 50A, 100A (mohato oa 3 o lekantsoeng ka nako e le 'ngoe)
Lebelo: Range 20.00m/s qeto 0.01m/s phoso 0.5%
Maeto:
Mefuta | Range | Qeto | Phoso |
Seqhoa sa vacuum | 50.0 limilimithara | 0.1 limilimithara |
0.5% |
SF6 sekhechana sa potoloho | 300.0mm |
1mm | |
Olimohatelli oa potoloho | 600.0mm |
Hona joale: mefuta e fapaneng ea 20.00A, qeto ea 0.01A
Matla a tsoang: DC 0-300V digital adjustable/20A (ho sebetsa hang-hang), qeto 1V.
Litekanyo: hoo e ka bang 360mm (L)* 280mm (W)* 300mm (H)
Boima ba 'mele: hoo e ka bang 10kg
Ka sehloohongunit e nang le letlapa la 10.1-inch | 1 leqc |
Nyeoe ea lisebelisoa | 1 pc |
Charger bakeng sa letlapa | 1 pc |
Adapter e tloaelehileng ea Amerika | 2 likhomphutha |
Rotary kutlo ea lebelo | 1 pc |
Sensor lebelo la mola50 limilimithara | 1 pc |
thapo ya kgokelo ya lebelo (5-terata e sirelelitsoeng ka mantlha) | 1 pc |
Ho bula le ho koala thapo ea taolo(3-core sheathed cable) | 1 pc |
Sehlohla sa kantlelemohathapo (e khubelu/e ntšo, 2-core) | 1 pc |
Cable ea fatše | 1 pc |
Ikopanye le thapo ya teko(4-core sheathed cable) | 1pc |
Cthapo e atolositsoeng ea tlhahlobo ea ontact (5M, e mosehla, e tala le e khubelu karolo e 'ngoe le e' ngoe, 3pcs e ntšo) | 6likhomphutha |
Cable e khutšoanyane (0.5m e ntšo,2m ntsho) | 2 likhomphutha |
Thapo ea matla | 1 pc |
Universal Joint le magnet base | 1 beha |
Lisebelisoa tse khethehileng tsa ho kenya tse tsitsitseng | 1 sete |
Lekola likarolo le lithupa | 1li-pcs tse 8 |
Contact resistance cable(5M) | 1 pc |
Pampiri ea ho hatisa | 2 meqolo |
Mohala oa USB | 1 pc |
Tataiso ea mosebelisi | 1 pc |
Tlaleho ea tlhahlobo ea fektheri | 1 pc |