GD6900 Capacitance le Dissipation Factor Tester
GD6900 e lekanya matla le dielectric loss factor (tgδ) ea lisebelisoa tsa motlakase tse phahameng.Ke sebopeho se kopantsoeng, borokho ba tlhahlobo ea tahlehelo ea dielectric e hahelletsoeng, phepelo ea motlakase e feto-fetohang, e matlafatsang transformer le SF6 capacitor e tloaelehileng.
Mohloli o phahameng oa motlakase o hlahisoa ke inverter e ka hare ea sesebelisoa, e sebelisetsoang ho hlahloba ntho ea teko ka mor'a ho matlafatsa motlakase.Haeba o eketsa kopi ea ho pata le sesebelisoa sa taolo ea mocheso, tahlehelo ea dielectric ea oli e sireletsang e ka lekoa.
●Tšoara skrineng sa LCD.
●Tekanyo ea ho hanyetsa mocheso: Mojule oa teko ea ho hanyetsa mocheso o hahelletsoeng, o ka etsa Insulation resistance (IR), absorption ratio (DAR), tlhahlobo ea polarization index (PI).
●Khalendara chip le polokelo e kholo ka hare.Boloka sephetho sa tlhahlobo ho latela tatellano ea nako, hlahloba rekoto ea nalane 'me u hatise sephetho.
●Lintlha tsa sesebelisoa li ka romelloa ka U disk.
●Mekhoa e mengata ea liteko, e nang le mekhoa ea ka hare ho motlakase o phahameng, ka ntle ho motlakase o phahameng, maemo a ka hare, maemo a ka ntle, GST / UST, ho ithabisa.Teko ea tahlehelo ea dielectric e phahameng (ho feta 10kV) e ka etsoa maemong a maemo a kantle kantle ho motlakase o phahameng.
●Lekola CVT e tiisitsoeng ka botlalo (Capacitive Voltage Transformer) C1 le C2 tahlehelo ea dielectric le capacitance ka nako e le 'ngoe.Hape leka karo-karolelano ea phetoho ea CVT le phapang ea angle ea voltage.
●Tahlehelo ea dielectric le boleng ba capacitance ea C0 karolong e ka holimo ea CVT e ka lekanyetsoa ka ho sebelisa mokhoa oa ho sireletsa ka morao.
●Letšoao le phahameng la sampole.Inverter le sampling potoloho ka hare li digitized laoloa.Matla a tsoang a lula a fetoha.
●LCR tekanyo e iketsang.Inductance, capacitance, resistance, angle e ka lekanngoa le ho bontšoa.
●Tšireletso e mengata ea ho feto-fetoha ha motlakase oa motlakase, sekhechana se sekhuts'oane se hlahisoang, motlakase o fetelletseng, o fetelletseng hona joale, mocheso, o bolokehile ebile o ts'epahala.Ho sa le joalo, e na le mosebetsi oa ho etsa liteko tsa motheo, hore motlakase oa motlakase ha o lumelloe bakeng sa lisebelisoa tse se nang motheo.
●Ha ho na tlhoko ea ho qhaqha HV lead ho lekanya tahlehelo ea dielectric le capacitance ea CVT.
●Maqhubu a ka fetoloa 50Hz, 47.5Hz/52.5Hz, 45Hz/55Hz, 60Hz, 57.5Hz/62.5Hz, 55Hz/65Hz.
Boemo ba ho sebetsa | -15 ℃ ~ 40 ℃ | RH<80% | ||||||
Molao-motheo o khahlanong le ho kena-kenana | Phetoho ea makhetlo | |||||||
Phepelo ea motlakase | AC 220V±10%, 50/60Hz | Jenereithara e ka sebelisoa. | ||||||
Phallo e phahameng ea motlakase | AC 0.5KV~10KV (12kV boikhethelo) | E 'ngoe le e' ngoe ea 0.1kV | ||||||
Ho nepahala | 2% | |||||||
Max.jwale | 200mA | |||||||
Bokhoni | 2000VA | |||||||
Boiketsi ba ho tsosa matla | AC 0V~50V/15A | 50Hz, 60Hz maqhubu a le mong 45HZ/55HZ 47.5HZ/52.5HZ 55HZ/65HZ 57.5HZ/62.5HZ Othomathiki habeli maqhubu | ||||||
Qeto | tgδ: 0.001% | Cx: 0.001pF | ||||||
Ho nepahala | ∆tgδ: ±(bala*1.0%+0.040%) | |||||||
∆C x: ±(ho bala*1.0%+1.00PF) | ||||||||
Lekhalo la litekanyo | tgδ | Ntle le moeli | ||||||
C x | 15pF <Cx <300nF | |||||||
10KV | Cx <60 nF | |||||||
5KV | Cx <150 nF | |||||||
1KV | Cx <300 nF | |||||||
Tlhahlobo ea CVT | Cx <300 nF | |||||||
Lethathamo la tekanyo ea LCR | L>20H(2kV) | R>10KΩ(2kV) | ||||||
Ho nepahala ha tekanyo ea LCR | 0.1% | Qeto | 0.01 | |||||
Karolelano ea CVT | 10 ~ 10000 | |||||||
Ho nepahala ha karo-karolelano ea CVT | 0.1% | |||||||
Qeto ea karo-karolelano ea CVT | 0.01 | |||||||
Insulation resistance | Matla a phahameng a DC | 5-10kV | Ho nepahala | ±(2%*Ho bala +10V) | ||||
Ho nepahala ha IR | 100kΩ-1000GΩ: <5% (teko ea motlakase e seng ka tlase ho 250V) 100GΩ-1000GΩ: 10% (teko ea motlakase e seng ka tlase ho 10000V) | |||||||
Boemo | Sehlopha se seholo: 350(L)×270(W)×270(H) | |||||||
Lebokose la lisebelisoa: 350(L)×270(W)×160(H) | ||||||||
Bokhoni ba memori | Lihlopha tse 200, polokelo ea disk ea USB flash e tšehetsoa. | |||||||
Boima ba 'mele | Sehlopha se seholo: 22.75Kg | |||||||
Lebokose la lisebelisoa: 5.25Kg |
Mohlahlobi | 1 sete |
Kesi ea lisebelisoa | 1 sengoathoana |
Tlhahlobo e khubelu ea HV e etella pele 8m | 1 sengoathoana |
Tlhahlobo e ntšo ea LV e etella pele 8m | 1 sengoathoana |
Thapo ea matla 1.8m | 1 sengoathoana |
CVT Connecting lead 5m | 1 sengoathoana |
Moeta-pele oa fatše 2m | 1 sengoathoana |
Pampiri ea ho hatisa | 2 meqolo |
10A fuse | 3 likotoana |
Tataiso ea mosebelisi | 1 khopi |
Tlaleho ea teko ea fektheri | 1 khopi |
Lisebelisoa tsa boikhethelo | |
Oli Test cell | 1 pc |
Selaoli sa ho futhumatsa | 1 pc |
Ka selefouno ea tlhahlobo ea oli le sesebelisoa sa ho futhumatsa, mosebelisi a ka leka tan delta ea mokelikeli oa dielectric joalo ka oli ea transformer.
Selaoli sa ho futhumatsa
Sekepe sa oli